MODEL AH-22

AH-22-12AH-22-32AH-22-34
Thermostat ControlModulatingModulatingModulating
Btu/Hr:2,000,0002,000,0002,000,000
Maximum Btu/hr:2,000,0002,000,0002,000,000
Minimun Btu/Hr12,00012,00012,000
CFM11,00011,00011,000
Max. External Static PressureUp to 2" ESPUp to 2" ESP Up to 2" ESP
Fan Type:Forward CurvedForward CurvedForward Curved
Discharge Diameter:24"24"24"
Voltage:1 Phase, 208 Volt3 Phase, 208 Volt3 Phase, 480 Volt
Current Consumption:40 amps22 amps11 amps
Recommended Fuse Size:75 amps40 amps20 amps
Fuel TypeNG or Vapor PropaneNG or Vapor PropaneNG or Vapor Propane
Natural Gas Consumption:600 CFH Lo-Fire - 2,000 CFH Hi-Fire600 CFH Lo-Fire - 2,000 CFH Hi-Fire600 CFH Lo-Fire - 2,000 CFH Hi-Fire
Propane Consumption:6.6 GPH / 21.8 GPH6.6 GPH / 21.8 GPH6.6 GPH / 21.8 GPH
Pressure Range1 - 25 lbs.1 - 25 lbs.1 - 25 lbs.
Temperature Control DischargeYesYesYes
Air Proving Safety:YesYesYes
Flame Sensing SafetyYesYesYes
Net Weight2,200 lbs.2,200 lbs.2,200 lbs.
Data SheetAH-22 Data SheetAH-22 Data SheetAH-22 Data Sheet
NEMA Plug Configuration:N/AN/AN/A
High Limit DischargeYesYesYes
Dimensions:60" x 101" x 64"60" x 101" x 64"60" x 101" x 64"